Yoshitake GP-1000EN Steam Pressure Reducing Valve, Ductile Cast Iron

Yoshitake GP-1000EN pressure reducing valve for steam. Features ductile cast iron body, stainless steel trim, and EN PN16 RF flanged connection. Max inlet pressure 1.0 MPa, max temperature 220°C.

Yoshitake GP-1000EN Steam Pressure Reducing Valve, Ductile Cast Iron

The Yoshitake GP-1000EN is a high-performance pressure reducing valve designed for steam applications. It features a ductile cast iron body and stainless steel trim, equipped with an EN PN16 RF flanged connection. The spherical main valve offers excellent sealability, greatly reducing valve seat leakage to comply with ANSI Class IV standards.

Features

  • Significantly improved workability and durability compared with conventional pressure reducing valves.
  • Spherical main valve offers great sealability and great reduction of valve seat leakage (compliant with ANSI Class IV).
  • Compliant with SHASE-S106 Pressure Reducing Valves (by the Society of Heating, Air-Conditioning and Sanitary Engineers of Japan).
  • Simple and robust internal structure.

Yoshitake GP-1000EN product photo

Specifications

SpecificationValue
ApplicationSteam
Inlet pressure0.1 - 1.0 MPa
Reduced pressure0.05 - 0.9 MPa (90% or less of inlet pressure)
Minimum differential pressure0.05 MPa
Maximum pressure reduction ratio20:1
Maximum temperature220°C
Valve seat leakage0.01% or less of rated flow
Body MaterialDuctile cast iron
Valve, valve seat MaterialStainless steel
Piston, Cylinder MaterialBrass or bronze
ConnectionEN PN16 RF flanged

INFO

Available with trim parts (piston and cylinder) made of stainless steel (GP-1000ENS).

Dimensions and Weights

Yoshitake GP-1000EN structural drawing

SizeL (mm)H1 (mm)H (mm)Flange D (mm)Flange C (mm)Flange t (mm)n-hWeight (kg)
15A150642919565164-148.0
20A1506429110575164-148.5
25A1606730012585184-1410.0
32A18082333140100204-1914.0
40A20082333150110204-1915.5
50A23093353165125204-1921.0
65A290100357185145214-1930.0
80A310122404210160288-1937.0
100A350144450254180328-1957.0

Selection Charts

Nominal Sizes Selection Chart (For Steam)

Yoshitake GP-1000EN Yoshitake GP-1000EN nominal sizes selection chart for steam

[Example 1] When selecting the nominal size of a pressure reducing valve whose inlet pressure (P1), reduced pressure (P2), and steam flow rate are 0.6 MPa, 0.4 MPa, and 800 kg/h, respectively, first find intersection point (A) of the inlet pressure of 0.6 MPa and the reduced pressure of 0.4 MPa. Trace down vertically from this intersection point to find intersection point (B) with the flow rate of 800 kg/h. Since intersection point (B) lies between nominal sizes 40A and 50A, select the larger one, 50A.

[Example 2] When selecting the nominal size of a pressure reducing valve whose inlet pressure (P1), reduced pressure (P2), and steam flow rate are 0.8 MPa, 0.05 MPa, and 600 kg/h, respectively, first find intersection point (C) of the inlet pressure of 0.8 MPa and the diagonal line. Trace down to the left from this intersection point to find intersection point (D) with the reduced pressure of 0.05 MPa. Trace down vertically from intersection point (D) to find intersection point (E) with the flow rate of 600 kg/h. Since intersection point (E) lies between nominal sizes 32A and 40A, select the larger one, 40A.

TIP

Set the safety factor at 80 to 90%.

Specifications Selection Chart

Yoshitake GP-1000EN Yoshitake GP-1000EN specifications selection chart Find the intersection point of the inlet and reduced pressures. If the intersection point is within any of the ranges shown in the chart above, the pressures are controllable. (Range A and C cover GP-1000 Series).

Corrected Cv Value

Yoshitake GP-1000EN Yoshitake GP-1000EN corrected cv value chartExample: Take a pressure reducing valve whose inlet pressure is 0.8 MPa, the reduced pressure is 0.05 MPa. Find the inlet and reduced pressure intersection point (A) at the above chart, then draw a horizontal line in the leftward direction to point (B) which indicates a correction coefficient of 0.85. For a nominal size of 25A, the corrected Cv value would be calculated as follows (based on formula in source).

Pressure Characteristic Chart

Yoshitake GP-1000EN Yoshitake GP-1000EN pressure characteristic chart This chart shows variation in reduced pressure when the inlet pressure of 1.0 MPa is changed between 0.3 MPa and 1.0 MPa while the reduced pressure is set at 0.1 MPa.

Safety Valve Setting

Set pressure of safety valve for alarm use at the outlet side of the pressure reducing valve for steam:

Set pressure of pressure reducing valve (MPa)Set pressure of safety valve (MPa)
0.1 or lessSet pressure of the pressure reducing valve + 0.05 or more
0.11 - 0.4Set pressure of the pressure reducing valve + 0.08 or more
0.41 - 0.6Set pressure of the pressure reducing valve + 0.1 or more
0.61 - 0.8Set pressure of the pressure reducing valve + 0.12 or more
More than 0.8Set pressure of the pressure reducing valve + 15%

INFO

When a safety valve is installed for alarm use at the outlet side of a pressure reducing valve for steam and there are no laws or regulations specified to comply with, select a safety valve whose blowout capacity is around 10% of the maximum flow rate of the pressure reducing valve.

Flow Rate Table (Partial)

(kg/h)

P1 (MPa)P2 (MPa)15A20A25A32A40A50A65A80A100A
10.05922123696008311,4782,3103,3265,913
0.1-0.41323035288581,1882,1123,3004,7528,448
0.51272925088261,1452,0353,1804,5808,142
0.61172694687611,0531,8732,9274,2157,494

::: note When the inlet pressure is more than 0.7 MPa and the pressure reduction ratio is more than 10:1, calculate the corrected Cv value by multiplying the rated Cv value by the correction factor C obtained from the chart. :::