TLV T8N / T10N and TF8N / TF10N cast iron compact sight glasses with flow indicating ball for steam, water, and air. Max pressure 13 barg.

TLV T8N / T10N and TF8N / TF10N are lightweight cast iron sight glasses designed for installation at the outlet side of steam traps to monitor trap performance and check for steam leakage. They are also recommended for checking the line flow of air and water, and are suitable for small-to-large flow rates.


INFO
Construction of the T(F)10N(L) differs from that of the T(F)8N(L) only in that there is a through-hole in the partition between the inlet and outlet, making them suitable for use with large flow rates.
| No. | Description | Repair Kit |
|---|---|---|
| 1 | Body | |
| 2 | Sight Glass | ✓ |
| 3 | Glass Holder | |
| 4 | Ball | ✓ |
| 5 | Gasket | ✓ |
| 6 | Nameplate | |
| 7 | Guard Plate | ✓ |
| Model | T8N / T10N | TF8N / TF10N |
|---|---|---|
| Connection | Screwed | Flanged |
| Size (DN) | 1/2", 3/4", 1", 1 1/4", 1 1/2", 2" | DN 15, 20, 25, 40, 50 |
| Maximum Operating Pressure (barg) PMO | 13 | 13 |
| Maximum Operating Temperature (°C) TMO | 200 | 200 |
| Applicable Fluids | Steam, Water, Air | Steam, Water, Air |
WARNING
Do not use for toxic, flammable or otherwise hazardous fluids. Maximum Allowable Pressure (PMA): 13 barg. Maximum Allowable Temperature (TMA): 200 °C. These are pressure shell design conditions, not operating conditions. Contact TLV for optional models T8NL/TF8NL/T10NL/TF10NL up to 150 °C.
| No. | Description | Material | DIN | ASTM/AISI |
|---|---|---|---|---|
| 1 | Body | Cast Iron FC250 | 0.6025 | A126 Cl.B |
| 2 | Sight Glass | Heat-resistant Tempered Glass | - | - |
| 3 | Glass Holder | Cast Iron FC250 | 0.6025 | A126 Cl.B |
| 4 | Ball | Fluorine Resin PTFE | PTFE | PTFE |
| 5 | Gasket | Fluorine Resin PTFE | PTFE | PTFE |
| 6 | Nameplate | Stainless Steel SUS304 | 1.4301 | AISI304 |
| 7 | Guard Plate | Mica | - | - |

Install a check valve on the outlet side if there is the danger of downstream water hammer!

Operational Check:
Operational inspections should be performed at least twice a year, or as called for by the operating conditions.
| Part | Inspection |
|---|---|
| Gaskets | Check for warping or damage |
| Glass | Check for fractures or cracks |
| Guard Plate | Check for fractures or cracks |
| Ball | Check for deformation |
Tightening Torque:
| Problem | Cause | Remedy |
|---|---|---|
| Cannot see through glass (Ball not visible) | The glass is dirty; Guard plate is dirty; Build-up of dirt inside the body | Clean glass / guard plate / body |
| Liquid leaks to the outside of the product | Deterioration or damage to gaskets; Improper glass holder tightening torque; Glass or guard plate damaged | Replace gaskets / glass / guard plate; Tighten to proper torque |
| Glass becomes damaged | Operating pressure or temperature exceeds maximum specified conditions; Glass outlived service life | Compare specs and actual conditions; Replace glass |
| Ball does not move (T8N/TF8N) | Body is clogged with dirt, or build-up on the ball | Clean parts |