Spirax Sarco BC3150 Blowdown Controller manages steam boiler TDS levels. Features continuous, purge, or pulsed outputs, IR communications, and 4-20mA retransmit.

Spirax Sarco BC3150 is a blowdown controller for steam boilers. It controls TDS (total dissolved solids - salts in solution) by opening and closing a blowdown valve. The product works by controlling the conductivity of liquids, in conjunction with a Spirax Sarco conductivity sensor (CP10, CP30, or CP32) and a boiler blowdown valve or condensate dump valve.
Designed for harsh industrial environments, the controller is equipped with a 3-digit LCD graphic display and features continuous, purge, or pulsed output modes. It provides a 4-20mA retransmit output and supports infrared (IR) communications between adjacent controllers.
The BC3150 is widely used in Boiler Control Systems for comprehensive TDS management. 

The Spirax Sarco CCD system monitors and displays the conductivity of condensate return, redirecting the flow to drain if conductivity increases above a pre-set level. 
The front panel provides direct access to parameter viewing and manual testing without entering the full password-protected commissioning menu. 
Manual Test Buttons
The BC3150 must be installed in a suitable industrial control panel or fireproof enclosure. It can be mounted on a 35 mm DIN rail, a chassis plate, or directly in a panel cutout. 
Electrical Safety
Isolate the mains supply before touching any of the wiring terminals. The design relies on the building installation for overcurrent protection.

Signal and Probe Wiring Maximum cable length for all probes is 100 m (for 9990 and 999.0 ranges), 10 m (9.990 range), or 30 m (99.90 range). 
| Parameter | Specification |
|---|---|
| Mains voltage | 110 V to 240 Vac at 50/60 Hz |
| Power consumption | 7.5 W (maximum) |
| Ambient temperature | 0 - 55 °C (32 - 131 °F) |
| Enclosure rating (front panel) | NEMA type 4 hose down only, IP65 |
| Parameter | Specification |
|---|---|
| Probe types | CP10, CP30 and CP32 |
| Conductivity ranges | 0 - 9.99, 0 - 99.9, 0 - 999, 0 - 9990 ppm or μS/cm |
| TC Sensor type | Pt100 – Class B or better |
| 4-20 mA Output | Minimum 0 mA, Maximum 20 mA (500 ohm max load) |
| Relay Contacts | 2 × single pole changeover relays (SPCO), 3 amp @ 250 Vac |
| Error message | Cause | Action |
|---|---|---|
| 1 Power out | Loss of power during operation | Check wiring and power supply |
| 2 Setup menu time out | No key pressed for 5 minutes | Re-enter commissioning mode |
| 3 Alarm 1 | High TDS alarm occurred | Check boiler operation and feedwater quality |
| 4 Alarm is latched! | Safety lockout triggered | Enter password in setup mode to clear |