BURKERT Type 8652 AirLINE valve island optimised for process automation. Features LC display, Hot Swap, AirLINE Quick, and ATEX/IECEx Zone 2 approvals.

BURKERT 8652 AirLINE valve island has been especially developed for process automation requirements. New diagnostic functions can be visualised on the LC display, both in clear text as well as symbols. This makes it easy to relate to the shown messages and helps to save time during start-up and maintenance. Furthermore, the diagnostic message is also available at the controller, enabling a fast overview of the plant status.
The hardware is optimised for installation at the bottom of the control cabinet. Installation on a standard rail is also possible. Key pneumatic functions ensure increased process reliability; for instance, check valves in the exhaust air ducts make sure there is no unplanned actuation due to pressure peaks.

| Property | Value |
|---|---|
| Body Material | PA (polyamide) |
| Seal Material | NBR and PUR |
| Width per station | 11 mm |
| Number of valve slots | Max. 24 |
| Maximum number of valve functions | Max. 48 |
| Pressure range | Vac...10 bar |
| External supply air | 3...10 bar |
| Flow rate QNn value air | 310 l/min (measured at +20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure) |
| Operating voltage | 24 V DC (±10% tolerance) |
| Nominal power of each valve | 0.7 W (0.175 W after power reduction) |
| Operating medium | Oil-free or lubricated compressed dry air, neutral gases (5 μm filter recommended) |
| Ambient temperature | -10 °C...+55 °C |
| Degree of protection | IP20, IP65 in closed control cabinets |
AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.
Advantages

The valve island supports various standard circuit functions (CF) and SIA variants for safety-related shut-off:
Supported interfaces include PROFIBUS DP, Industrial Ethernet (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic), PROFINET S2, CANopen, and büS.
Hot Swap Installation Clearance
To use the Hot Swap function, always observe a minimum distance to the front edge of the control cabinet when installing the valve island inside the control cabinet. Please also refer to the detailed description in the operating instructions.

The digital inputs are supplied (24 V) by the electronic module. Current is limited to maximum 30 mA per digital input. Standard 3-wire sensors and 2-wire sensors with voltages between 10…30 V as well as mechanical limit switches can be used.
Type 6534 valves are equipped with additional connection terminals. A valve circuit can therefore be interrupted by an external switch. Manual override is not required for these valve variants. To use the shut-off function, connect the terminal to a potential-free contact (mechanical switch or relay).
The following illustration shows a network with the example of AirLINE Type 8652 with Industrial Ethernet variant as master valve terminal and various AirLINE Type 8652 with büS variant as slave valve terminals.

When using the device in a potentially explosive area, special conditions apply:
Danger caused by voltage
Danger of explosion due to electrostatic charge
Special conditions for using the Hot Swap function
The use of the Hot Swap function is prohibited in an existing explosive atmosphere. If it can be proven and ensured by means of suitable test equipment that there is no explosive atmosphere for a certain period of time, it is permissible to remove/insert valves using Hot Swap during this time.