BURKERT 20142853 Type 8647 AirLINE SP 8-Bank Electropneumatic Valve Island (REV.2, AirLINE Quick VA)

BURKERT 20142853 is an 8-bank AirLINE SP Type 8647 REV.2 valve island with stainless steel AirLINE Quick base, G 1/4 ports, D6 push-in connections, P HotSwap, check valves in 3/5, and Siemens SIMATIC ET 200SP integration.

BURKERT 20142853 Type 8647 AirLINE SP 8-Bank Electropneumatic Valve Island (REV.2, AirLINE Quick VA)

BURKERT 20142853 is an 8-bank AirLINE SP Type 8647 electropneumatic valve island configured for direct integration into Siemens SIMATIC ET 200SP and ET 200SP HA distributed I/O systems. Built in Generation Revision 2 (REV.2) with an 11 mm station pitch, it features an AirLINE Quick stainless steel base adapter plate with bottom-facing D6 push-in working connections and G 1/4 supply ports. The unit incorporates pneumatic HotSwap on supply channel 1 (P) and integrated check valves in exhaust ports 3 (R) and 5 (S), supporting operating pressures from 2.5 bar to 10 bar across an ambient operating temperature range of 0 °C to +55 °C.

BURKERT 20142853 Type 8647 AirLINE SP valve block overview

System Architecture & Distributed I/O Integration ​

AirLINE SP Type 8647 operates as a combined electro-pneumatic automation platform that latches directly into the Siemens SIMATIC backplane bus. Electrical connections for load voltage, backplane communication, and functional grounding are established automatically upon mechanical engagement with the adjacent SIMATIC ET 200SP BaseUnits. Configuration and parameterization occur natively within Siemens engineering environments such as TIA Portal (via HSP or GSDML), SIMATIC STEP 7 Classic (via HSP or GSD), and SIMATIC PCS 7 (via Hardware Update Package HUP).

Station Power Supply Rule

Install a light-colored BaseUnit (BU...D or BU...D/T) directly to the left of the valve block to provide a dedicated load voltage feed. For SIMATIC ET 200SP HA installations, this separate power supply segment is mandatory. Load voltage tolerance is ±10% at 24 V DC, which must be observed to prevent undervoltage trips on pilot solenoid coils.

Integration constraints between the distributed I/O families must be evaluated during engineering:

System CharacteristicSIMATIC ET 200SP StationSIMATIC ET 200SP HA Station
Hardware mountingStandard DIN rail (TH 35)ET 200SP HA profile rail
BaseUnit upstream of valve blockRecommended (BU...D or BU...D/T)Mandatory (BU...D or BU...D/T with cover)
Multiple valve blocks per stationYes (with separate power feed)No (maximum 1 valve block per station)
Expansion modules to the rightPermissible (light BaseUnit required)Not permitted (must terminate with server module)
AirLINE Quick base adaptationPermissibleNot supported due to mechanical layout
Engineering toolsTIA Portal (HSP/GSDML), STEP 7 (HSP/GSD)PCS 7 (HUP) from V9.0 SP2, GSDML

AirLINE Quick Stainless Steel Cabinet Base Adaptation ​

BURKERT 20142853 includes the AirLINE Quick base adapter constructed from stainless steel (1.4301 / 1.4401). Instead of routing pneumatic tubing through external cabinet glands, the AirLINE Quick plate installs directly into a rectangular cut-out at the bottom of the control cabinet. The valve block sits inside the enclosure while pneumatic supply, exhaust, and all D6 working lines exit directly downwards from the cabinet floor.

BURKERT 20142853 AirLINE Quick stainless steel base adapter plate

This mounting method eliminates individual tube feed-through glands, decreases internal cabinet volume requirements, and achieves an IP65 enclosure seal (UL Type 4X verified in closed cabinets). When mounted with AirLINE Quick, the rigid metal adapter plate carries the mechanical load, supporting the standard DIN rail and attached ET 200SP electronic slices.

BURKERT 20142853 control cabinet base mounting with AirLINE Quick

Cabinet Base Installation Requirements

Ensure the cabinet cut-out is burr-free prior to seating the sealing gasket into the AirLINE Quick plate groove. Fix the external stability plate using M5×10 screws tightened to 2.0 Nm. Rail projection beyond the valve block perimeter must not exceed 10 cm on either side.

Pneumatic Specifications & HotSwap Technology ​

The 8-bank pneumatic assembly operates over a pressure range of 2.5 bar to 10 bar using filtered, neutral gaseous media (ISO 8573-1:2010 Class 7.4.4 with 5 µm particle limits). Monostable pilot valves (Type 6524 3/2-way and Type 6525 5/2-way) deliver a nominal flow rate (QNn) of 300 l/min. Double valves (Type 6524 2×3/2-way) also deliver 300 l/min.

BURKERT 20142853 pneumatic supply and exhaust port assignment

Connection PositionMarking / IdentificationFunctionThread / Dimension
Position 1R/3, S/5Common deaeration / exhaust ductsG 1/4 (internal thread)
Position 2XAuxiliary pilot air / pilot exhaustM5
Position 3P/1Main compressed air supplyG 1/4 (internal thread)

Pneumatic working lines are mapped at the individual valve positions:

BURKERT 20142853 working connection assignment for valve units

Port Location3/2-Way Valve (Type 6524)2×3/2-Way Valve (Type 6524)5/2-Way Valve (Type 6525)
Upper port 1Not used (remains plugged)Working port 2 (A)Working port 2 (A)
Lower port 2Working port 2 (A)Working port 4 (B)Working port 4 (B)

Tightening Torques for Connections

Adhere to defined port torques during assembly: G 1/4 supply ports P and R/S require 4.0 Nm to 7.0 Nm (maximum 20 Nm); M5 pilot ports require 1.0 Nm to 1.2 Nm (maximum 3.0 Nm); M7 push-in connectors require 1.75 Nm to 2.25 Nm (maximum 4.0 Nm); valve block rail clamping screws require 1.8 Nm.

Pneumatic HotSwap and Non-Return Protection ​

BURKERT 20142853 features integrated P-channel HotSwap check valves. Individual valves can be unscrewed and replaced while the main air supply remains pressurized. In Generation REV.2, the internal HotSwap check valve geometry reduces nominal flow by approximately 20% (improved from up to 50% flow reduction in REV.1). Integrated non-return check valves in exhaust ducts 3 (R) and 5 (S) prevent backpressures from migrating into adjacent actuators during safety shutdown or high-cycle exhausting.

Operational Safety Warning

Before replacing pilot valves on modules without P HotSwap, depressurize and vent all feed lines. Under P HotSwap operation, detaching a valve depressurizes ports A or B, which can cause connected actuators to move unexpectedly. Secure all mechanical actuators against movement before service.

Revision 2 (REV.2) Distinguishing Characteristics ​

BURKERT 20142853 belongs to Generation Revision 2 (REV.2). REV.2 incorporates significant mechanical and pneumatic design standardizations compared to earlier REV.1 units:

Mechanical / Pneumatic FeatureGeneration REV.1Generation REV.2 (Model 20142853)
Push-in collet release ring colorBlackBlue
Working port channel arrangementParallel alignmentWavy (staggered) alignment
Pilot valve interface flangeFlange profile FM14 (single valves)Standardized flange profile FM20
Double valve interface flangeFlange profile FM20Standardized flange profile FM20
Flow restriction with P HotSwapUp to 50% reductionApproximately 20% reduction
Type label markingsStandard marking without revision noteExplicit label designation "Rev.2"

Flange Interface Compatibility

Single valves Type 6524 (3/2-way) and Type 6525 (5/2-way) with REV.1 FM14 flanges cannot be mounted onto REV.2 pneumatic base modules. REV.2 base modules accept only standardized FM20 replacement valves. Double valves Type 6524 (2×3/2-way) share the FM20 pattern and remain mechanically interchangeable.

Electrical Data & Safety Shutdown Options ​

The valve block draws coil power directly from the 24 V DC power bus of the SIMATIC ET 200SP BaseUnits. Power consumption is 0.8 W per single valve coil (1.6 W per 2×3/2-way valve). All electronic base modules contain electronic self-resetting short-circuit fuses and module-level blow fuses.

Three functional methods exist for safety-related valve shutdown:

  1. Block-Level De-energization: Cutting load voltage to the upstream light BaseUnit immediately de-energizes all pilot valves across the island, forcing monostable valves back to their unactuated mechanical rest positions.
  2. Siemens F-PM-E Power Module Integration: Placing the valve block within the potential group of a Siemens fail-safe power module (F-PM-E 24VDC/8A PPM ST) enables certified safety shutdown according to EN ISO 13849-1 and IEC 62061. This requires all PQ modules and connection units to carry the "FC" mark.
  3. External Valve Shutdown (EVS): Electronic base modules equipped with an EVS header provide a 2-pole terminal (0.14 mm² to 1.5 mm², AWG 28-16) for module-specific shutdown via an external potential-free contact (e.g., Siemens RQ or F-RQ relay output).

EVS Wiring Restriction

Connect the EVS terminal only to potential-free switching contacts rated for 1.5 A at 24 V DC. Do not apply external voltage to EVS terminals. Never link EVS terminals from multiple modules in parallel; each module requires its own dedicated isolated contact. Limit wiring run to a maximum of 2 m within the same control cabinet.

Diagnostic Functions & Switching Cycle Monitoring ​

Electronic base modules (PQ modules) communicate operational data through the Siemens backplane bus and display real-time statuses on dual LC displays. Channel output states, position feedbacks, and active system modes (such as PROFIenergy or active EVS shutdown) are presented graphically.

Each valve channel provides two separate 32-bit switching cycle counters:

  • Pilot Valve Counter: Monitors the physical actuations of the pilot flipper coil on the valve block.
  • Actuator Counter: Monitors actuations of the driven process valve or cylinder in the field.

Counters persist in remanent memory and can be evaluated or reset acyclically using SIMATIC data records DS 130 (pilot counter read), DS 131 (actuator counter read), and DS 132 (counter reset). Predictive maintenance limits can be parameterized to trigger control alarms when defined operating thresholds are reached.

Replacement Valves & Spare Parts ​

Maintenance and modular expansion of the 8-bank BURKERT 20142853 assembly must utilize genuine REV.2 spare components:

Component DescriptionCircuit Function / SpecificationOrder Article No.
Type 6524 Solenoid Valve (REV.2)3/2-way NC, 2.5–10 bar, 24 V DC, manual override20029918
Type 6524 Solenoid Valve (REV.2)3/2-way NO, 2.5–10 bar, 24 V DC, manual override20029919
Type 6524 Solenoid Valve (REV.2)3/2-way NC, Vac–7 bar, auxiliary pilot air20029923
Type 6525 Solenoid Valve (REV.2)5/2-way, 2.5–10 bar, 24 V DC, manual override20029920
Type 6524 Double Valve (REV.1/REV.2)2×3/2-way NC, 2.5–10 bar, 24 V DC, manual override204710
Blanking cover plate (REV.2)For unused slots: Type 6524/6525 REV.2 & 2×3/2-way661092
Electrical connector coverCovers unused electrical socket on PQ module653670
Spare profile valve seals FM24For Type 6524 3/2-way REV.2 (pack of 12)20024336
Spare profile valve seals FM20For Type 6524 2×3/2-way & Type 6525 REV.2 (pack of 12)20016305
AirLINE Quick blind plate8-fold blind plate covering cut-out20057390
Tube support sleevesFor push-in D6 PU flexible tubing (pack of 10)20099400