Skip to content
ATEX/IECEx Zone 2PROFINET S2Hot SwapAirLINE Quick

BURKERT 20138252 8652 AirLINE Valve Island

Burkert Type 8652 AirLINE valve island for process automation. Features up to 24 valve slots, Industrial Ethernet, LC display, and ATEX/IECEx Zone 2 explosion protection.

BURKERT 20138252 8652 AirLINE Valve Island

BURKERT 8652 AirLINE valve island has been especially developed for process automation requirements. New diagnostic functions can be visualised on the LC display, both in clear text as well as symbols. This makes it easy to relate to the shown messages and helps to save time during start-up and maintenance. Furthermore, the diagnostic message is also available at the controller, enabling a fast overview of the plant status. The hardware is optimised for installation at the bottom of the control cabinet, though installation on a standard rail is also possible. Key pneumatic functions ensure increased process reliability, such as check valves in the exhaust air ducts that prevent unplanned actuation due to pressure peaks.

BURKERT 20138252 BURKERT 8652 AirLINE valve island overview

General Technical Data ​

Product propertiesDescription
MaterialBody: PA (polyamide)
Seal: NBR and PUR
Width per station11 mm
Number of valve slotsMax. 24
Maximum number of valve functionsMax. 48
Pressure rangeVac...10 bar
External supply air3...10 bar
Flow rate QNn value air310 l/min (measured at +20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure)
Operating voltage24 V DC (±10% tolerance)
Nominal power of each valve0.7 W (0.175 W after power reduction)
Operating mediumOil-free or lubricated compressed dry air, neutral gases (5 μm filter recommended)
Degree of protectionIP20, IP65 in closed control cabinets
Ambient temperature-10 °C...+55 °C

AirLINE Quick ​

AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.

Advantages:

  • Reduced space requirement in the control cabinet
  • This makes it possible to use more compact control cabinets
  • Reduced installation effort due to hose connections directly at the bottom of the control cabinet

BURKERT 20138252 BURKERT 8652 AirLINE Quick Adapter in stainless steel or anodised aluminium

Circuit Functions ​

The Type 8652 supports various standard circuit functions via the Type 6534 replacement valves:

  • Circuit function C (CF C): 3/2-way solenoid valve, servo-controlled, normally closed.
  • Circuit function D (CF D): 2 × 3/2-way solenoid valve, servo-controlled, normally open.
  • Circuit function H (CF H): 5/2-way solenoid valve, servo-controlled.
  • Circuit function L (CF L): 5/3-way solenoid valve, in middle position all ports locked.
  • Circuit function M (CF M): 5/3-way solenoid valve, in middle position ports 2 and 4 ventilated.
  • Circuit function N (CF N): 5/3-way solenoid valve, in middle position ports 2 and 4 exhausted.
  • Circuit function Z (CF Z): 5/2-way solenoid valve, impulse variant with 2 coils.

SIA Variant

SIA variants are available for safety-related shut-off. These valves are equipped with additional connection terminals, allowing a valve circuit to be interrupted by an external switch.

Approvals and Conformities ​

  • Explosion protection: ATEX (II 3G Ex ec IIC Gc / II 3D Ex tc IIIC Dc) and IECEx (Ex ec IIC Gc / Ex tc IIIC Dc). Suitable for zone 2/22.
  • North America: UL Listed (UL 61010-1) and UL Recognized for Hazardous Locations (Class I, Zone 2 / Class II, Zone 22 / Class I, II, III, Division 2).
  • China Compulsory Certification (CCC): Products with Ex approval are suitable for import and use for hazardous applications in China.

Dimensions ​

Variant 4-, 8- and 12-fold ​

BURKERT 20138252 BURKERT 8652 Dimensions for 4-, 8- and 12-fold variants

VariantABCmn
4-fold66-4 x M531
8-fold351118 x M572
12-fold7715410 x M5113

Variant 16-, 20- and 24-fold ​

BURKERT 20138252 BURKERT 8652 Dimensions for 16-, 20- and 24-fold variants

VariantABCDmm'n
16-fold with intermediate supply11222410 x M5114.3774
20-fold with intermediate supply13426810 x M5158.31175
24-fold with intermediate supply15631210 x M5158.311116

Product Connections ​

Power supply for communication and displays ​

Connect 5-pin spring-loaded terminal according to the pin assignment (Possible cable cross-section: ≤ 1.5 mm²).

PinColourAssignment
1Red24 V DC
2WhiteCAN_H (büS connection)
3GreenSHIELDING
4BlueCAN_L (büS connection)
5BlackGND

Power supply for pneumatic valves ​

The interface plate has a 2-pin spring-loaded terminal to which the pneumatic valves' power supply is connected.

ClipColourAssignment
1RedAUX 24 V
2BlackGND

Product Installation ​

Hot Swap in Explosion Hazard Areas

The use of the Hot Swap function is prohibited in a present explosive atmosphere. If it can be proven and ensured by means of suitable test equipment that there is no explosive atmosphere for a certain period of time, it is permissible to remove/insert valves using Hot Swap during this period.

To use the Hot Swap function, always observe a minimum distance to the front edge of the control cabinet when installing the valve island inside the control cabinet.

Example Configuration ​

The following illustration shows a network with the example of AirLINE Type 8652 with Industrial Ethernet variant (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic) as master valve terminal and various AirLINE Type 8652 with büS variant as slave valve terminals.

BURKERT 20138252 BURKERT 8652 Example network configuration with Industrial Ethernet