Burkert Type 8652 AirLINE valve island for process automation. Features up to 24 valve slots, Industrial Ethernet, LC display, and ATEX/IECEx Zone 2 explosion protection.

BURKERT 8652 AirLINE valve island has been especially developed for process automation requirements. New diagnostic functions can be visualised on the LC display, both in clear text as well as symbols. This makes it easy to relate to the shown messages and helps to save time during start-up and maintenance. Furthermore, the diagnostic message is also available at the controller, enabling a fast overview of the plant status. The hardware is optimised for installation at the bottom of the control cabinet, though installation on a standard rail is also possible. Key pneumatic functions ensure increased process reliability, such as check valves in the exhaust air ducts that prevent unplanned actuation due to pressure peaks.

| Product properties | Description |
|---|---|
| Material | Body: PA (polyamide) Seal: NBR and PUR |
| Width per station | 11 mm |
| Number of valve slots | Max. 24 |
| Maximum number of valve functions | Max. 48 |
| Pressure range | Vac...10 bar |
| External supply air | 3...10 bar |
| Flow rate QNn value air | 310 l/min (measured at +20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure) |
| Operating voltage | 24 V DC (±10% tolerance) |
| Nominal power of each valve | 0.7 W (0.175 W after power reduction) |
| Operating medium | Oil-free or lubricated compressed dry air, neutral gases (5 μm filter recommended) |
| Degree of protection | IP20, IP65 in closed control cabinets |
| Ambient temperature | -10 °C...+55 °C |
AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.
Advantages:

The Type 8652 supports various standard circuit functions via the Type 6534 replacement valves:
SIA Variant
SIA variants are available for safety-related shut-off. These valves are equipped with additional connection terminals, allowing a valve circuit to be interrupted by an external switch.

| Variant | A | B | C | m | n |
|---|---|---|---|---|---|
| 4-fold | 66 | - | 4 x M5 | 3 | 1 |
| 8-fold | 35 | 111 | 8 x M5 | 7 | 2 |
| 12-fold | 77 | 154 | 10 x M5 | 11 | 3 |

| Variant | A | B | C | D | m | m' | n |
|---|---|---|---|---|---|---|---|
| 16-fold with intermediate supply | 112 | 224 | 10 x M5 | 114.3 | 7 | 7 | 4 |
| 20-fold with intermediate supply | 134 | 268 | 10 x M5 | 158.3 | 11 | 7 | 5 |
| 24-fold with intermediate supply | 156 | 312 | 10 x M5 | 158.3 | 11 | 11 | 6 |
Connect 5-pin spring-loaded terminal according to the pin assignment (Possible cable cross-section: ≤ 1.5 mm²).
| Pin | Colour | Assignment |
|---|---|---|
| 1 | Red | 24 V DC |
| 2 | White | CAN_H (büS connection) |
| 3 | Green | SHIELDING |
| 4 | Blue | CAN_L (büS connection) |
| 5 | Black | GND |
The interface plate has a 2-pin spring-loaded terminal to which the pneumatic valves' power supply is connected.
| Clip | Colour | Assignment |
|---|---|---|
| 1 | Red | AUX 24 V |
| 2 | Black | GND |
Hot Swap in Explosion Hazard Areas
The use of the Hot Swap function is prohibited in a present explosive atmosphere. If it can be proven and ensured by means of suitable test equipment that there is no explosive atmosphere for a certain period of time, it is permissible to remove/insert valves using Hot Swap during this period.
To use the Hot Swap function, always observe a minimum distance to the front edge of the control cabinet when installing the valve island inside the control cabinet.
The following illustration shows a network with the example of AirLINE Type 8652 with Industrial Ethernet variant (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic) as master valve terminal and various AirLINE Type 8652 with büS variant as slave valve terminals.