BURKERT 20120106 Type 8652 AirLINE 24-Valve Modular Valve Island with PROFINET S2

BURKERT 20120106 Type 8652 AirLINE is a 24-bank modular valve island with PROFINET S2 redundancy, 48 digital inputs, HotSwap capability, and ATEX/IECEx Zone 2/22 approval.

BURKERT 20120106 Type 8652 AirLINE 24-Valve Modular Valve Island with PROFINET S2

BURKERT 20120106 (Type 8652) AirLINE is a 24-bank modular pneumatic valve island engineered to control pneumatic actuators and process valves within automated process architectures. Built on an aluminium AirLINE Quick (ALQ AL) interface with brass pneumatic connections, this configured assembly incorporates 20 positions of 5/2-way monostable (CF-H) valves, one 3/2-way (CF-C) valve, and three blind plates. It integrates PROFINET S2 system redundancy over dual RJ45 hardware ports and includes six electronic input modules providing 48 digital inputs for direct feedback signal acquisition.

Operating across a nominal pressure span from -1 bar to 10 bar with pilot control pressure between 3 bar and 10 bar, the unit functions in ambient and fluid media temperatures ranging from -10 °C to +55 °C. For process continuity and safety, the assembly integrates pneumatic HotSwap functionality on supply port 1 (P), internal pilot air supply, and integrated check valves in exhaust ducts 3 (R) and 5 (S). Certified versions with order codes PU17 or PX68 comply with ATEX Directive 2014/34/EU, IECEx schemes, NEC classifications, and CCC standard GB/T 3836-2021 for Zone 2 and Zone 22 hazardous locations.

BURKERT 20120106 Type 8652 AirLINE modular pneumatic valve island overview

Valve Island Configuration (Ident Code 20120106) ​

The configured 20120106 valve island combines pneumatic valves, base plate mechanics, and fieldbus communication into a pre-tested assembly.

Configuration ParameterSpecification Value
Type Family8652 AirLINE
Ident Number (SKU)20120106
Total Valve Slices24 PCE
Valve Positions 1 to 205/2-way monostable, circuit function H (CF-H)
Valve Position 213/2-way, circuit function C (CF-C)
Valve Positions 22 to 24Blind plate (reserve positions)
Supply Port ConnectionD10 push-in, Brass
Working Port ConnectionsD6 push-in, Brass
Adapter Plate InterfaceAirLINE Quick, Aluminium
Pilot Air ConfigurationInternal auxiliary pilot air
Intermediate Feed1 PCE (no additional left, right, or middle external feeds)
Check ValvesIntegrated check valves in port 3 (R) and port 5 (S)
HotSwap CapabilityPneumatic HotSwap integrated on port 1 (P)
Communication ProtocolPROFINET S2 (system redundancy)
Physical InterfaceDual RJ45 industrial Ethernet ports
Digital Inputs48 DI total across 6 electrical input modules (8 DI each)
Enclosure RatingIP20 (with mating connectors attached)

Terminology and Functional Definitions ​

The Type 8652 documentation defines technical abbreviations and system components as follows:

TermDefinition within System Documentation
Actuator / Process ValvePneumatic load controlled by the 8652 valve island
büSBürkert communication bus based on CANopen protocol architecture
EVSExternal valve shutdown: closes valves in a de-energized state independently of fieldbus master signals; configurable per valve, valve module, or entire block
Potentially Explosive AtmosphereHazardous industrial areas subject to gas or dust explosion risks
Device / Valve IslandAirLINE Type 8652 modular valve island assembly
SIA VersionSafety Integrated Architecture version dedicated to certified safety shutdowns (refer to EVS)
Pneumatic Valve / Pilot ValvePneumatic spool valves integrated into the block, piloted by Type 6164 miniature solenoids

Hazardous Location Operation and Enclosure Requirements ​

When deployed under hazardous area supplementary specifications (options PU17 and PX68), Type 8652 must be installed within certified industrial control cabinets meeting structural environmental ratings.

  • Gas Atmosphere Enclosure (Ex ec / Category 3G / Zone 2): Must be installed inside an enclosure meeting EN/IEC 60079-0 and EN/IEC 60079-7 requirements with a minimum ingress protection rating of IP54.
  • Dust Atmosphere Enclosure (Ex tc / Category 3D / Zone 22): Must be installed inside an enclosure meeting EN/IEC 60079-0 and EN/IEC 60079-31 requirements with an ingress protection rating of at least IP6X (minimum IP64).
  • Pollution Degree: Operation is restricted to environments with a pollution degree of at least 2 in accordance with IEC 60664-1.
  • Overvoltage Transient Protection: External transient suppression must prevent line surges from exceeding 140% of the nominal peak supply voltage.
  • Supply Voltage Stability: The rated 24 V DC supply must not exceed nominal voltage by more than 10% continuously, nor exceed 40% transiently.
  • Outdoor Use Restriction: Outdoor operation is strictly prohibited.
  • Electrostatic Precaution: Clean exterior surfaces solely using a damp or antistatic cloth to prevent electrostatic discharge in hazardous zones.

Electrical Isolation in Potentially Explosive Atmospheres

In the presence of an explosive atmosphere, terminal connections for the 24 V DC power supply, SIA, EVS, and digital inputs must only be connected or disconnected when completely de-energized. Fixed cable plugs into terminal blocks must likewise be manipulated only with connected circuits switched off. Disconnecting energized circuits risks incendiary sparking.

Special Conditions for HotSwap Operation

Pneumatic HotSwap enables replacement of individual valve slices under line pressure. Within potentially explosive atmospheres, HotSwap valve removal or insertion is strictly prohibited unless atmospheric testing instruments verify that no explosive gas or dust concentration is present throughout the entire service intervention. Only trained personnel may execute HotSwap procedures.

Hazardous Area Approvals and Marking Plates ​

Type 8652 AirLINE valve islands approved for hazardous zones carry two identification plates: the standard operational rating plate and an Ex compliance plate.

BURKERT 20120106 Type 8652 general product nameplate layout and data field arrangement

General Product Nameplate Structure ​

PositionParameter DescriptionField Data Example
1Device TypeType 8652 AirLINE
2Pressure Range3 to 10 bar (pilot control pressure)
3Ambient Temperature Range-10 °C to +55 °C
4Rated Voltage / Current Consumption24 V DC / 3 A
5Serial NumberS/N (factory assigned)
6Manufacturing CodeW14AL (encoded date/batch)
7Order Code (Ident Number)20120106 (or configured 8-digit ident)

BURKERT 20120106 Type 8652 supplementary hazardous area nameplates for PX68 and PU17 configurations

Hazardous Area Marking Plate Layout (Code PX68) ​

PositionDescriptionApproval Data
1Explosion Protection LogoCommunity Ex hexagon mark
2ATEX Certificate NumberBVS 20 ATEX E 031 U
3ATEX Gas / Dust MarkingII 3G Ex ec IIC Gc / II 3D Ex tc IIIC Dc
4IECEx Certificate NumberIECEx BVS 20.0024 U
5IECEx Gas / Dust MarkingEx ec IIC Gc / Ex tc IIIC Dc
6Safety Advisory SymbolReference to electrical disconnection and HotSwap limits

Hazardous Area Marking Plate Layout (Code PU17) ​

PositionDescriptionApproval Data
1US/CA Zone Marking (Gas)Cl I, ZN 2, AEx ec IIC Gc / Ex ec IIC Gc U
2US/CA Zone Marking (Dust)Cl II, ZN 22, AEx tc IIIC Dc / Ex tc IIIC Dc U
3US/CA Division MarkingCl I, Div 2, Gr A, B, C, D / Cl II, III, Div 2, Gr F, G
4ATEX Certificate NumberBVS 20 ATEX E 031 U
5Explosion Protection LogoCommunity Ex hexagon mark
6ATEX Gas / Dust MarkingII 3G Ex ec IIC Gc / II 3D Ex tc IIIC Dc
7IECEx Certificate NumberIECEx BVS 20.0024 U
8IECEx Gas / Dust MarkingEx ec IIC Gc / Ex tc IIIC Dc
9Safety Advisory SymbolReference to electrical disconnection and HotSwap limits

Every hazardous location shipment includes an auxiliary adhesive warning label: WARNING DO NOT CONNECT OR DISCONNECT WHEN ENERGIZED. If cabinet geometry obscures the primary Ex plate, this warning sticker must be affixed in a clearly visible location on the valve island.

Technical Operating Data and Permissible Configurations ​

Type 8652 systems comply with DEKRA testing standards (BVS 44809 Bochum) and production quality surveillance by PTB (CE 0102). China Compulsory Certification (CCC) is verified by SITIIAS in compliance with GB/T 3836-2021.

Operating ParameterPermissible Value / Criterion
Rated Supply Voltage24 V DC ±10%
Nominal PowerArchitecture-dependent
Ambient Temperature Range-10 °C to +55 °C
Solenoid Pilot ValvesType 6164 (acting as pilot operators for Type 6534 main valves)
Maximum Number of Valve Slices48 valve functions maximum
Temperature Class ComplianceT4 limit is maintained at cabinet internal ambient temperatures up to +55 °C
AirLINE Quick External Surface TempMaximum outer cabinet surface temperature does not exceed 80 °C
Permissible Hazardous Location Assembly Options

Under BVS 20 ATEX E 031 U and IECEx BVS 20.0024 U, permissible modular variations include combinations of up to 48 valve functions using Type 6534 pneumatic valves, Type 6534 SIA safety variants, external valve shutdown (EVS) modules, digital input electronic slices, and pressure sensor modules. Configurations with fewer than 48 valve functions dissipate less electrical power, resulting in equal or lower operating temperatures.