Skip to content
IEEE 802.15.4Up to 400°CIntrinsically Safe

TLV iT5-ZB-SUN Wireless Surface Temperature and Ultrasonic Monitoring Sensor

TLV iT5-ZB-SUN wireless monitoring sensor for steam traps and equipment. Features surface temperature (up to 400°C) and ultrasonic measurement via IEEE 802.15.4 protocol. Intrinsically safe.

TLV iT5-ZB-SUN Wireless Surface Temperature and Ultrasonic Monitoring Sensor

The TLV iT5-ZB-SUN is a wireless sensor designed for monitoring a large quantity of crucial steam-using equipment such as heat exchangers, presses and turbines, equipment in difficult-to-reach locations, or steam traps via TLV's IEEE 802.15.4-based protocol. It provides surface temperature and ultrasonic measurement capabilities.

Features

  • Suitable for monitoring many devices: up to 8000 sensors can be connected to one data station.
  • Measurement cycles configurable between 5 minutes and 24 hours.
  • Low power consuming device powered by a long-life battery pack.
  • Surface temperature measurement up to 400 °C.
  • Intrinsically safe construction for use in hazardous and non-hazardous locations.

INFO

Steam trap diagnostic software is required separately. Contact TLV for details. Patented.

TLV iT5-ZB-SUN wireless monitoring sensor overview

Specifications

General Specifications

ParameterValue
Wireless Frequency Band2.4 GHz
Maximum No. of Connections100 repeaters and 8000 sensors per data station
Maximum No. of Hops20 (from sensor to data station)
Measurement Cycle5 minutes to 24 hours
Power SourceNon-rechargeable lithium-thionyl chloride battery pack (3.6V, 19 Ah)
Battery Life10 years (30 min cycle) or 5 years (15 min cycle)

Temperature Specifications

TypeLow TemperatureHigh Temperature
Maximum Measurement Temperature (°C)250400
Measurable Temperature Range (°C)-40 to +250-40 to +400
Max Ambient Temp (Meas. Temp -40 to < 135°C)8080
Max Ambient Temp (Meas. Temp 135 to < 200°C)7575
Max Ambient Temp (Meas. Temp 200 to < 250°C)67-
Max Ambient Temp (Meas. Temp 200 to < 300°C)-67
Max Ambient Temp (Meas. Temp 300 to < 400°C)-62

Note: Intrinsic safety standards (ATEX, IECEx, UL/cUL) apply. Refer to individual specification data sheets (SDS) for full compliance details.

WARNING

Confirm location is non-hazardous before performing battery replacement. Product failure due to flexible pipe vibrations etc., is not covered by the warranty. Battery life is given for 25°C ambient temperature and may be shorter than expected based on environmental conditions and installation location. Contact TLV for further information.

TLV iT5-ZB-SUN dimensions or supplementary details

System Configuration Example

TLV iT5-ZB-SUN system configuration example

No.ModelFunction
Sensor: iT5-ZB-SUNMeasurement of ultrasound and surface temperature, wireless transmission of information
Repeater: iT5-ZB-RUNWireless relay of information
Data Station: iT5-ZB-DSNRelay of information via intranet
Data Collection ServerImporting collected data