Skip to content
FOUNDATION™ FieldbusIntrinsically SafeMax 400 °C

TLV iT5-FF-SUN Monitoring Sensor for Surface Temperature and Ultrasonic Measurement

The TLV iT5-FF-SUN is a monitoring sensor for surface temperature and ultrasonic measurement based on FOUNDATION™ Fieldbus, designed for reliable high-frequency monitoring of steam-using equipment.

TLV iT5-FF-SUN Monitoring Sensor for Surface Temperature and Ultrasonic Measurement

The TLV iT5-FF-SUN is a monitoring sensor designed for reliable, high-frequency monitoring of crucial steam-using equipment such as heat exchangers, presses and turbines, equipment in difficult-to-reach locations, or steam traps. It features surface temperature and ultrasonic measurement based on the FOUNDATION™ Fieldbus protocol.

Features ​

  • High frequency monitoring: measurement cycles configurable between 1 and 15 seconds.
  • Wired network connection enables reliable data communication.
  • Surface temperature measurement up to 400 °C.
  • Intrinsically safe construction for use in hazardous and non-hazardous locations.

Note

Steam trap diagnostic software is required separately. Contact TLV for details.

TLV iT5-FF-SUN monitoring sensor overview

Specifications ​

ParameterLow Temperature TypeHigh Temperature Type
Maximum Measurement Temperature (°C)250400
Measurable Temperature Range (°C)-40 to +250-40 to +400
Communication StandardFOUNDATION™ FieldbusFOUNDATION™ Fieldbus
Power SourceSupplied by FOUNDATION™ FieldbusSupplied by FOUNDATION™ Fieldbus
Maximum No. of Connections32 devices (using TLV-recommended linking device)32 devices (using TLV-recommended linking device)
Segment ExtensionUp to 4 repeaters arranged in series per segmentUp to 4 repeaters arranged in series per segment
Measurement Cycle1 to 15 seconds1 to 15 seconds
Electrical Rating & Intrinsically Safe Standards

FISCO

  • Power circuit Allowable voltage: 17.5 V
  • Allowable current: 380 mA
  • Allowable power: 5.32 W
  • Internal inductance: 10 μH
  • Internal capacitance: 5 nF

ENTITY

  • Power circuit Allowable voltage: 24 V
  • Allowable current: 250 mA
  • Internal inductance: 10 μH
  • Internal capacitance: 0

Dimensions ​

iT5-FF-SUN Straight Pipe

TLV iT5-FF-SUN straight pipe dimensions

Units: mm, Weight: approx. 900 g

System Configuration Example ​

TLV iT5-FF-SUN system configuration example

No.ModelFunction
①Sensor: iT5-FF-SUNMeasurement of ultrasound and surface temperature, transmission of information
②TerminalFieldbus device connection, relay and branching
③RepeaterRelay of Fieldbus information between linking device and terminal or between terminals over long distances and power supply
④Linking Device and Power SupplyRelay of Fieldbus information and power supply
⑤Data Collection ServerImporting collected data